At controller inhibit, the display 'Output frequency with slip compensation' is not set to 0

Which products are affected?

8200vector 0.25 - 90 kW (≤ SW 3.1)
8200motec 0.25 - 7.5 kW (≤ SW 3.1)

What happens?

In the operating mode 'Vector control', when the controller is inhibited and the process controller is switched off (C0238 = 2), code C0051 ('Output frequency with slip') indicates the value of the slip instead of 0 Hz.

When does the problem occur?

This function restriction occurs when the operating mode 'Vector control' (C0014 = 4) is active, the process controller is not used (C0238 = 2) and the controller is inhibited.

Possible diagnostics?

Reading code C0051 when the controller is inhibited.

Short-term measures/recommendations?

When the controller is inhibited, the display C0051 is not relevant.

Evaluation

When the controller is inhibited, code C0051 indicates a wrong value. Actually, 0 Hz should to be indicated since when inhibited, the output stages do not output any rotating field frequency. Since the drive is inhibited, the display is not relevant.