Standardised input of the frequency setpoint in percent of the maximum output frequency
Which products are affected?
8200vector 0.25 - 90 kW (≤ SW 3.1) with standard I/O or application I/O (≤ SW 3.1)
8200motec 0.25 - 7.5 kW (≤ SW 3.1) with standard I/O or application I/O (≤ SW 3.1)
What happens?
It is impossible to select standardised setpoints in percent of the maximum output frequency (with the selection C0127 = 1 and C0412/1 = 255) via the parameter channel (C0141) of a communication module.
When does the problem occur?
The function restriction occurs when trying to select a standardised setpoint in percent of the maximum output frequency via the parameter channel of a communication module.
Possible diagnostics?
A standardised setpoint selection via the parameter channel is impossible. The drive does not rotate.
Short-term measures/recommendations?
Setpoint selection via process data channel or via parameter channel C0046 (no possibility for standardisation in the frequency inverter).
Evaluation
The problem is detected during set-up. The speed of the drive differs from the desired speed.