Which products are affected?
8200vector/motec ≤ SW3.0
What happens?
If parameter sets are transferred by using the keypad the error message TRIP Er081 may be indicated.
When does the problem occur?
If the values under C0080, C0185, C0310; C0608 (default setting) differ from the ones of the keypad (customer-specific parameters) the check sum is not generated correctly after the parameter set transfer.
Possible diagnostics?
Reading out error memory C0161
Short-term measures/recommendations?
Do not change the Lenze default setting made under C0185, C0080, C0310 and C0608. After the parameter set transfer the codes mentioned before can be modified manually by using the keypad.
Evaluation
Failure has been eliminated with software version 3.1.