Standby operation and PARAM-RD

Which products are affected?

9300EP servo positioning controller version V2.1

What happens?

POS-PARAM-RD = HIGH is without function during standby operation.

When does the problem occur?

The change in travel profile parameters with POS-PARAM-RD = HIGH during the standby operation was not possible. For example, change in ultimate velocity in order to make a flying change to positioning, without any change in velocity.

Possible diagnostics?

POS-PARAM-RD is without function during standby operation.

Short-term measures/recommendations?

Possibly adapt travel profile parameters using FEVAN; the duration of value transfer with FEVAN is, however, longer than with POS-PARAM-RD.

Evaluation:

Uncritical, work around is possible.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/20035125/1/