Master current input 4...20 mA, SD5 monitoring, required settings

Question:

Master curent input 4...20 mA and SD5 monitoring, which settings are necessary?

Answer:

The analog input 1 (AIN1; terminals X6/1 and X6/2) can also be used as master current input. The following settings are necessary:
  • Connect the upper two pins (5,6) of programming plug connector X3 with the attached jumper (see also operating instructions chapter 'Control connections')
  • Set C0034 to  -1- for master current 4...20 mA.
  • If necessary, the SD5 monitoring for the master current input 4..20 mA can be activated under C0598 (trip or warning). This monitoring is inactive in the default setting.

Note:
The master current mode -20...+20 mA can also be set under C0034. In this mode, the SD5 monitoring is naturally always inactive.