Which slave profiles have AS-i slaves (AS-i field bus function module E82ZAFFC and on-board AS-i of motor starter starttec)?

Answer:

AS-i slaves have two identifications which are called slave profiles. The slave profile consists of an ID code (identification of AS-i slave) and an I/O code (configuration of I/O data).

ID code:
  • ID code:   Fh
  • ID code1: Fh
  • ID code2: Fh
I/O code:
  • I/O conf: 7h
Note:The I/O configuration (7H) specifies 4-bit inputs and outputs. Lenze components do not use all I/O data.
  • AS-i field bus function module E82ZAFFC: 4-bit inputs and 2-bit outputs
  • AS-i on-board of motor starter starttec: 3-bit inputs and 2-bit outputs
These settings must not be modified!