How can the dead time of a touch probe sensor ie kann die Totzeit eines Touch-Probe-Sensors bei der Verwendung der DDS-Bibliothek LenzeTpDrv.lib kompensiert werden?
Answer:
The function L_TpConfigDigInX is used to configure a dead time compensation from a POU of the PLC project. The compensation is provided in increments. Manufacturer specifications of time must be converted into a distance [inc] by multiplying with the current speed [inc/ms]. For this, the function L_TpConfigDigInX and the calculation in a time-controlled task, preferably with short interval, must be called. The longer the intervals, the more inaccurate the localisation from the TP signal, since a speed change between the task requests is not considered.
Note: Use this function or signal conditioning only in a task with high-priority and short interval.