External 24 V supply, reverse voltage protection for digital outputs
Application:
External evaluation of fault signals from the Regenerative Power Supplies 9340 at terminals X2/A1 and X2/A2
Description:
Depending on the HW status (see e.g. rating plate EMB934X-X.HW.SW) the supply/energy recovery model is protected against reverse voltage from the external 24 V supply:
HW <= 1G: If the 24 V control voltage is reversed and terminals 39 and 59, the digital outputs will be damaged beyond repair if the continuous current of the supply voltage is not restricted by external precautions. For the purpose of protection a 250 mA miniature fuse can be fitted, for example.
HW >= 1H: The Regenerative Power Supply is protected against reverse control voltage when connecting up.
Taxonomy:
Regenerative power supply unit EMB9341
,
Regenerative power supply unit EMB9342
,
Regenerative power supply unit EMB9343
,
Regenerative power supply unit 9340
AKB-ID:
20020545
Last update:
2023/09/08
Category:
Version Informations