DC injection brake, permanent connection with drive control via fieldbus

Which products are affected?

EVF93XX-EV.XX.21
Drive control via field bus (Profibus, Interbus)

What happens?
If the controller is enabled the drive indicates under C0183 (drive status) 'DC brk AIF' or 'DC brk C135'. However, a DC injection braking is not executed.

When does the problem occur?
AIF-CTRL.B4 or control word C135.B4 is permanently connected to the DC injection braking function although the bit can freely be assigned according the documentation (Manual, GDC).

Note:
If the communication modules and the DRIVECOM profile are used, it must be observed that the bit 5 control word is shown inversely on the AIF-CRTL.B4 bit.

Possible diagnostics?
The AIF-IN-CTRL.B4 output is used in the drive control.

Short-term measures/recommendations?
Use another free control bit instead of AIF-IN-CTRL.B4.

Evaluation:
The error immediately occurs during commissioning.