Parameter setting under code L-C2357 (monitoring times)

Difference description 2175IB SW V0.6 to V0.7

1. Product identification
  • article number new (V0.7): 403940 or 416657
  • construction labelling new: 2175IB.VB.07 or 2175IB.VC.07
  • ordering designation: EMF2175IB
  • article number old (V0.6): 403940

2. Function improvements

Application
When using the CanOpen communication profile the monitoring time can be set by under code L-C2357.

Description
During operation with the 9300 IEC1131 drive controllers modifications under code L-C2357 subcodes 1 to 3 (monitoring times for the single CAN channels) have not been adapted. As a result, the monitoring time has been set to 3000 ms although the code display has been changed.

Elimination
The behaviour described above has been eliminated in software version V0.7.

Short-term measure in the previous version
None

Possible diagnostics
The behaviour described above will occur if Fault indication CE1, CE2 or CE3 are indicated by the drive controller - although the monitoring has been deactivated by parameterising the monitoring time with 0 ms.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/20011190/1/