EtherCAT does not switch to 'Operational'

Corrected from: 
-

Behavior of the new version: 

-

 

 

Description of the behavior: 

  • The EtherCAT master of the controller does not switch to the 'Operational' state.
  • Although the message 'Start Download Service' appears in the logbook, the download service is not ended. The message 'Download Service done' does not appear.

Conditions under which the behavior occurs:
The behavior described above occurs if the application object, which is named 'Application' by default, is renamed in the PLC Designer project.

Affected products:
Cabinet Controller 
c430 from V1.0
Cabinet Controller c520 from V1.0
Cabinet Controller c550 from V1.0

Short-term measure, recommendations, evaluation:
Do not change the name of the 'Application' object in the device tree of the PLC Designer project.