"Save parameter sets" dialog in PLC Designer reports finished too quickly (fixed with V1.13)

Corrected from:
Cabinet Controller c430 V1.13
Behavior of the new version:
The PLC Designer dialog 'Save parameter set' shows the status 'Finished', when the saving of the parameter set is completed.


Description of the behavior:
The PLC Designer dialog 'Save parameter set' shows the status 'Finished' too early, although the saving of the parameter set on the controller c430 has not yet been completed. The dialog closes immediately afterwards.

Conditions under which the behavior occurs:
The behavior described above occurs when

  • a boot project is present on the controller c430
and
  • the parameter 0x231F:005 'Module ID: Network selection' was changed
and
  • the <Save parameter sets> button was clicked in the PLC Designer.

Affected products:
PLC Designer from V3.28

in conjunction with Cabinet Controller c430

Short-term measures, Recommendations,Evaluation:
Check the status of the parameter set saving via parameter 0x2022:003 ('Device command: Save Parameter setting'). You can use this parameter to start saving the parameter set directly.

[Automatic Translation]