Corrected from:
Communication module Profinet IO E94AYCER FV 3.1
Response of the new version:
The new module works perfectly on the Profinet network despite the use of the Siemens FB PROFIenergy.
What happens?
After a restart of the Siemens PLC, the Lenze 9400 Profinet is not accessible on the Profinet network.
The module also no longer responds to an Ethernet ping.
When does the behaviour occur?
If the FB for the PROFIenergy is used in the Siemens S7 for our 94xx PN device, the behaviour described above may occur.
Which products are affected?
Communication module Profinet IO E94AYCER FV 3.0
Short-term measures:
Do not use PROFIenergy with the 94xx Profinet module. PROFIenergy is not supported by the 94xx Profinet module anyway.
Automatic Translation