Behaviour in case of the Profinet Factory Reset command

Eliminated from:
E94AYCER communication module firmware version 1.40.

Behaviour of the new version?
In case of a Factory Reset command triggered by the Profinet master the module loads the parameters for the Lenze default setting.



Which products are affected?
E94AYCER communication module equipped with a firmware version lower than 1.40

What happens?
The module loads the parameters 0 for the IP addresses and quotation marks for the station names after a Factory Reset command.

When does the problem occur?
The behaviour occurs if a Factory Reset is triggered by the Profinet master.

Possible diagnostics?
If the Lenze Profinet module loads the value 0 for the IP parameters and quotation marks for the station name after a Factory Reset command from the Profinet master.

Short-term measures/recommendations?
None.

Evaluation:
Since a Factory Reset command should not be executed while the machine is running it cannot happen that the machine shows a faulty behaviour.