CANopen, assignment of COB IDs in the default setting in accordance with CANopen (from V2.0 onwards)

Function extension:
COB ID assignment occurs in the default setting in a manner compliant with CANopen. Using code L-C00353/1...3, the method for assigning COB IDs can be set as follows:
  • Node address + Lenze ID  (as previously for Lenze devices)
  • Node address + CANopen ID (as for CANOpen --> default setting)
  • Setting the COB ID directly

This means the following differences apply between firmwares V1.0 and V2.0 in the default setting of code L-C00353/x when assigning COB IDs:

COBID for PDOs   FW 1.0                             FW2.0  
CAN-IN1               200h + node address       200h + node address
CAN-OUT1            180h + node address       180h + node address
CAN-IN2               280h + node address       300h + node address
CAN-OUT2            281h + node address       280h + node address
CAN-IN3               300h + node address        400h + node address
CAN-OUT3            301h + node address      380h + node address

In which products/versions is it included?
8400 StateLine  SW V2.0 onwards

Applications
Using the frequency inverter in a CANopen network

Published with service message No. 2008/26

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200804526/1/