Parameter set file cannot be loaded into the drive controller

Which products are affected?
Global Drive Loader V3.0 SP2

9300 servo controller (0.37-75kW) V7.0
9300 positioning controller V7.0
9300 servo cam profiler V7.1
9300 Vector (0.37-90kW) V7.1
9300 Vector (0.37-90kW) V7.3
9300 Vector (110-400kW) V7.0
9300 Vector (110-400kW) V8.0
8200 Vector (0.25kW - 11kW) V3.7
8200 Motec (0.25kW - 2.2kW) V3.7
8200 Motec (3.00kW - 7.5kW) V3.7

What happens?
When the parameter set is downloaded the message window of the GD Loader indicates the following message:

The parameter transfer cannot be executed. Error! (C400h)

When does the problem occur?
The response described before occurs when the GD Loader is used to load a parameter set which has been generated for an older software version (firmware) into one of the drive controllers mentioned above.

Possible diagnostics?
None.

Short-term measures/recommendations?
  • Use the Global Drive Control to downlad the parameter set.
  • Use the Global Drive Control to convert the parameter set to the current drive controller version.
  • Install the device data update 7 or higher.

Evaluation:
The GD Loader cannot download a parameter set into the current drive controller version if the parameter set has been generated for an older drive controller version. The function restriction will be eliminated with the next device data update.