Faulty bus status indicated under C1530

Which products are affected?
E82ZAFUC CANopen fieldbus function module firmware version < 1.2 in combination with the 8200 vector/motec frequency inverter series or motor starter starttec

What happens?
If the CAN states 'Warning' or' Bus Off' are left the state displayed under code C1530 does not change.

When does the problem occur?
The problem occurs if it is changed to another CAN state out of the CAN states 'Warning' or 'Bus Off'.

Possible diagnostics?
The behaviour described before has occurred if the communication LED of the module which indicates the current CAN states indicates 'Operational' or 'Pre-Operational' and 'Warning' or 'Bus Off' is indicated under code C1530.

Short-term measure/recommendation
None.