During parameter set transfer by means of a keypad code L-C0009 is not correctly transferred

Which products are affected?
EMZ9371BB keypad and XT EMZ9371BC keypad.

How is the reaction?
Code L-C0009 is not transferred when parameter set transfer is made by means of a keypad.

When does the problem occur?
The keypads enable a parameter set to be transferred between two drive controllers of type 9300. For this purpose the parameter set must be stored non-volatile in the operating unit by means of code L-C0003 = 1. And it is to be transferred to the other drive controller with code C0002 = 20.

Possible diagnostics?
During parameter set transfer by means of a keypad the value in code C0009 is not modified.

Short-term measures/recommendations?
No.

Evaluation:
If you operate a communication module on the AIF interface, the field bus communication will eventually not be faultless after a parameter set transfer, as in code C0009 there is an incorrect node address.