Turning of absolute value encoders during download

Which products are affected?
EVS93xx-EI (Servo PLC Version 6.2 DSMC control board)
EVS93xx-ET (Servo PLC Version 6.2 DSMC control board)

What happens?
If the absolute value encoder of the motor is turned during the download, this movement is not recorded after starting the PLC program since the absolute value encoder is not read in again after the download. As a result, the position is lost and a crash might occur.

When does the problem occur?
If the motor shaft is turned during the program download.

Possible diagnostics?
None.

Short-term measures/recommendations?
Ensure that the motor shaft is not turned during the download, e. g. by an external brake.

Evaluation:
The error occurs immediately during commissioning in combination with a project download.