Limitation of the set magnetising current

Which products are affected?

9300 vector 0.37…90 kW SW V6.2

Function description

In the vector control mode (C0006 = 1) the setpoint of the magnetising current to be injected is calculated from the motor current data (C0088) and rated power factor (C0090). If the user enters a rated current under C0088 which is considerably larger than the rated current of the frequency inverter used an impermissible heating of the motor and the frequency inverter may occur. As a result the set magnetising current is limited to 66 % of the maximum output current of the frequency inverter.

Applications

Applications in which the frequency inverter is underdimensioned compared to the motor.