Support of the 4th process data word

Difference description 2175IB SW V0.6 to V0.7

1. Product identification
  • article number new (V0.7): 403940 or 416657
  • construction labelling new: 2175IB.VB.07 or 2175IB.VC.07
  • ordering designation: EMF2175IB
  • article number old (V0.6): 403940

2. Function improvements

Application
Four process data words are to be transferred when using the 9300 controller.

Description
With software version V0.6 it is only possible to transfer three process data words although the module should support the transfer of four process data words.

Elimination
From software version V0.7 onwards the 4the process data word (AIF-IN.W3) is also transferred from fieldbus module type 2175IB to the basic device (9300 drive controller) now. The standardisation of the process data is 16384dez = 100 % (This is also the case with all other 'analog' process data words).

Short-term measure in the previous version
None

Possible diagnostics
If the fourth process data word is tranferred by the PLC and the value is not indicated in the drive controller the problem described above will occur.