L_TT1P_TechnologyModules: xDone response does not correspond to PLCOpen specification (corrected from V3.12)

Corrected from:
L_TT1P_TechnologyModules_LM V3.12.0.9
 
Response of the new version:
If a request / an action has been successful, the xDone output switches to TRUE. The xDone output remains TRUE until the request is reset from TRUE to FALSE via xExecute. If the request has already been reset to FALSE via the xExecute input at this time, xDone remains TRUE for one cycle.
 

What happens?
The xDone output remains set to TRUE. 

When does this behaviour occur?
An xExecute technology module input is set and the corresponding action is executed. After this, the xExecute input is reset, before the action is completed.
 
Which products are affected?
All technology modules contained in the L_TT1P_TechnologyModules_LM library (V3.10.0.8 and higher)
 
Short-term measures:
xExecute should only be reset when the action has been completed.
  
Evaluation/recommendations:
Future alteration: After successful completion of an action, the xDone output will be set for one cycle.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500635/1/