Controller enable while the parameter set or default settings are loaded (eliminated from V5.0 onwards)
Eliminated from:
StateLine / HighLine with firmware version V05.01 or higher
Behaviour of the new version?
The inverter remains inhibited during the loading process, i.e. as long as the corresponding device command is active.
Display in C0158.
Which products are affected?
8400 StateLine / HighLine with FW < 05.01
What happens?
The controller can be enabled while the default settings or a parameter set are loaded. The behaviour of the drive and its outputs is undefined.
When does the problem occur?
While the corresponding device command is processed.
Short-term measures / recommendations?
Ensure that the controller remains inhibited until the loading process has finished.
Evaluation:
The error can be avoided if the recommendations are followed.
Taxonomy:
8400 HighLine frequency inverters
,
8400 StateLine frequency inverters