Function extension:
The following interference suppression filter can now be used for the single-phase 230V devices of the Servo Inverter i950 series:
- Low-Leakage (LL) 1.5kW 17A 1x230V LL (I0FAE215B100L0001S)
- Mains voltages 1x 230/240V
- for substructure and adjacent mounting.
- Rated current based on 40°C ambient temperature
Disturbance filter expression | INENN | Assignment Servo i950 | fSW |
BF3 1x 230/240V: LL | 17.0A | 0.37kW, 0.55kW, 0.75kW, 1.5kW | 2kHz ... 16kHz |
Net | TN, TT |
Phase | 1/N/PE |
Designated voltage (AC) | 230/240V |
Net frequency | 45Hz ... 65Hz |
- High-frequency interference emission and residual current
When installing a filter, both IT screws on the servo inverter i950 must be removed.
Type of protection | IP20 according to EN 60529 Type 1 NEMA |
Compliance with the limit values for the interference voltage at the mains terminal according to category C1 and C2 in each case with shielded motor cable in accordance with EN 61800-3.
Distortion filter Switching frequencies | Category and motor cable length shielded |
BF3 1x 230/240V: LL 2kHz ... 8kHz 2kHz ... 4kHz 2kHz ... 16kHz | C1 3 m C1 5 m C2 5 m |
Compliance with the residual current for operation on residual current circuit breaker (RCCB) type B with a rated residual current of 30mA. The limit value is 33%.
Disturbance filter | Trigger current and motor cable length shielded |
BF3 1x 230/240V: LL 2kHz ... 8kHz 2kHz ... 16kHz | 8% 3 m 10% 5 m |
Proof that the touch current is less than 3.5mA.
Disturbance filter | |
BF3 1x 230/240V: LL 2kHz ... 16kHz 2kHz ... 16kHz | 3.4 mA 3 m 3.4 mA 5 m |
Installation location | Control cabinet |
Installation position | Hanging, mounted behind frequency inverter,or mounted next to the frequency inverter |
Conformity, Explanations and evidence:
- CE conformity
- RoHS
- China-RoHS
- UL certificate (in progress)
- UKCA conformity
- REACH
Included in the following products:
Servo inverter i950 - all single-phase 230V devices, regardless of firmware version:
Application:
Use of the i950 230V devices in areas with high requirements for the interference category (C1, C2).
[Automatic Translation]