PLC-Designer V4 and older i950 device description: An exception of the soft PLC occurs when switching the TA (0x4000) (fixed from i950 device description V01.11.00)

Removed from:
PLC-Designer V4 with i950 device description  from V01.11.00
 
Behavior of the new version:
For with PLC-Designer V4 new projects to be created should only use i950 firmware from V01.11.00 as the target system.
 
Description of the behavior:
PLC-Designer V4:
If projects are created with older target system versions, exceptions may occur during application switching (0x4000), among other things.

Under what conditions does the behavior occur?

  • PLC-Designer V4 and
  • create new project with i950 FW <= V01.10.xx as controller and associated i950 device description.
Affected products:
  • PLC-Designer V4 with i950 device description 
Short-term measures, Rating/Recommendations:
For with PLC-Designer V4 new projects to be created should only use i950 firmware from V01.11.00 as the target system.

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500009/1/