Question:
There are two fieldbus couplers (IP20) in the IO system IO3000.
- w580_C_FB_001 (standard)
- w580_C_FB_002 (ECO)
What are the differences between the two fieldbus couplers?
Answer:
The table below shows the main differences between the two fieldbus couplers.
| w580_C_FB_001 (Standard) | w580_C_FB_002 (ECO) |
Number of modules | Max. 64 active | Max. 16 active |
Support of the following IO modules: - w560-C-1E-001 (UR20-2DI-P-TS)
- w560-C-2E-005 (UR20-4DI-P-TS)
- w540-C-2E-001 (UR20-4AI-I-HART-16-DIAG)
- w580-C-NT-001 (UR20-1COM-CANOPEN)
| Yes | No |
Support Distributed
Clocks (DC) | Yes | No |
USB diagnostic interface
(WebInterface) | Yes | No |
Operation
(horizontal assembly) | -20 °C
to +60 °C (2 x 10 A supply) | 0 °C ...
+50 °C (1 x 10 A supply) |
|
Operation
(vertical assembly) | -20 °C to +55 °C (2 x 8 A
power supply) | 0 °C ... +45 °C (1 x 10 A
power supply) |