No reservation of application credit for optional fieldbus interface at runtime

Corrected from:
-
Behavior of the new version:
-


Description of the behavior: 
No communication is possible via the optional EtherCAT slave or Profinet fieldbus interface.


Conditions under which the behavior occurs:
The behavior occurs when the application credits required for the optional fieldbus interface are sent via the block L_ILMP_SetAppCreditConfiguration of the L_ILMP_LicenseManager library from the PLC project.


Affected products:
Cabinet Controller c430 from V1.11


Short-term measures, Recommendations, Rating:
If you want to use the optional fieldbus interface, select in the License Manager of the object 'FAST_System_Configuration' the configuration 'Static AC Configuration' to assign the application credit in the field 'AC Device Feature', 

  • Switch (0 AC, default setting)
  • EtherCAT Device (100 AC)
  • ProfiNET Device (150 AC)
PLCD_AC Device Features 328_SSHOT.png

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202300416/1/