Protective measure "automatic disconnection of supply" of drive controllers

Frage:
Which Lenze products provide overcurrent or short-circuit protection according to IEC/HD 60364-4-41 (DIN VDE 0100-410) for the output circuits ?
 
Answer:
 Prerequisites for fault protection according to IEC/HD 60364-4-41 (DIN VDE 0100-410) for the output circuits of the devices i7x0; i9x0; 9400 are:


Installation in TN network and TT network

  • The inverters are installed according to the specifications in the documentation.
  • The system complies with the requirements of the applicable standards of the series IEC/HD 60364 (DIN VDE 0100).
  • The continuity of all associated PE and equipotential bonding conductors is ensured, including the connection and connection points.
  • Additional in the TT network:
    • The use of RCDs or additional protective grounding according to IEC60361-4-41 Section 415 is required.

Under these conditions, the mentioned inverters meet the protective measure "automatic disconnection of the supply" according to IEC/HD 60364-4-41 (DIN VDE 0100-410) Section 411.3.2.5 for the outputs U,V,W of the mentioned devices. I.e. in case of a short circuit with negligible impedance to a protective conductor or to earth, the inverters reduce the output voltage within the limits specified in Table 41.1 of IEC/HD 60364-4-41 (DIN VDE 0100-410) required time.


For the outputs +UG/-UG and Rb1/Rb2 applies:

lines for the DC link wiring (+UG/-UG) and for connecting the braking resistors Rb1/Rb2 must be selected in such a way that in the event of a fault (short-circuit, ground fault) upstream fuses interrupt the power supply or due to a short-circuit-proof wiring according to DIN VDE 0100-520:2013-06 a short-circuit or ground fault can be excluded. ground fault can be excluded.