L_TT1P_FlexCAM, L_TS2P_FlexCam: Changed cam disk is not processed in the next cycle (no change planned)

Removed from:
No change is planned for this behavior.
 
Description of the behavior:
The change of the y-values is not completely adopted in the curve slice. 
This leads to a possible position jump at the end of the profile.

Under what conditions does the behavior occur?
The interpolation points (e.g. lrY) are changed on the currently processed cam slice.e.g. lrY) are changed.

Affected products:
Technology module L_TT1P_FlexCamState from library L_TT1P_TechnologyModules_LM 
Technology module L_TS2P_FlexCamState from library L_TS2P_SynchronizingCamming

Short-term measures:
A second cam reference must be created and connected to the CamTable2 input.
If the base points are changed, CamTable1 must be switched to CamTable2 with the input wSetCamTable.
If you change the base points again, you can switch back to CamTable1 and so on.

Rating/Recommendations:
The FlexCam technology module looks at the CAM ID of the CamRef and the length of the x-axis to detect a change in the cam disk. In the event that the listed parameters are not changed, the cam plate is not updated. By taking the short-term measure into account, the required behavior can be fulfilled.  