L_TT1P_SmartTrack: Exception when using the TM (corrected from V3.24.0)

Corrected from:
Library: L_TT1P_TechnologyModules_LM (from V03.24.00)
              (Update via EASY Package Manager)

Response of the new version:
Access Violation does not occur under any circumstances.

What happens?
An AccessViolation occurs.

When does the behaviour occur?
Incorrect parameterisation:
The setting of the touch probe source (Tp from Master/Slave) does not match the touch probe position transferred.
In this case, access violations may occur.

Which products are affected?
L_TT1P_SmartTrack from library L_TT1P_TechnologyModules_LM

Short-term measures:
When setting the parameters, make sure that the axis connected to the touchprobe module is selected as the touchprobe in the TM.

Evaluation / recommendations: