Interruption of PROFINET IO communication after factory calibration Load or save parameter set

Corrected from:

Communication module Profinet IO E94AYCER FV 3.1

Response of the new version:
If the device command factory calibration is loaded or parameter set, there is no interruption of the Profinet IO communication.

 
What happens?
The command Load factory calibration or Save parameter set, via an existing Ethernet connection of the Profinet module, no longer leads to an interruption of the Profinet IO communication.

When does the behaviour occur?
The behaviour only occurs if the commands Load factory calibration or Save parameter set are executed via an existing Ethernet connection of the Profinet module (Engineer).

Which products are affected?
Communication module Profinet IO E94AYCER FV 3.0

Short-term measures:
Do not execute the device command Load factory calibration or Save parameter set via an existing Profinet connection. 
If the device command Load factory calibration or Save parameter set is executed via a diagnostic adapter connection, the Profinet IO communication is not interrupted.