Resetting the stored station structure in the I/O sytem 1000

Question:
How can you reset the stored station structure in the CAN bus coupler module of the I/O system 1000?

Answer:
The structure of the station is permanently stored via index I1010hex (Store parameter). If the real structure of the station no longer corresponds to the stored structure after a restart, the bus coupler module will report an error (red SF LED will be on).

The stored structure of the station is deleted via index I1011hex (Restore parameter). I. e. after mains switching for the I/O system following the restore command, the station error will no longer be pending – the SF LED will be off. The restore command resets all parameters of the I/O system to the Lenze setting.