i700 with Basic Safety - STO - Safe stop 1 with electronic safety relay - performance level e


Function:
When the safety function is requested, the motor is stopped according to stop category 1 of EN 60204-1.
The SS1 functionality is implemented in the 'SS1_Control' function block to be created.

 

The delay time of the safety relay must be longer than the resulting QSP time. The deceleration (units/s2) is selected via the lrQuickStopDec input of the L_SMC_AxisBasicControl FB. Consider the delay time tolerances of the safety relay.
The values to be set depend on the application.
In the drawing, the delay time of the safety relay is set to 3s.

Faults have been excluded for protected cables (according to DIN EN ISO 13849-2:2013-02 and IEC 61800-5-2:2008-04). This applies to cables which are protected by a cable duct and installed inside the control cabinet.

Safety information / disclaimer:

The safety application and parameterisation notes are examples of possible subfunctions in machines.

The T10D value according to DIN EN ISO 13849-1, Annex C.4.2 is only indicated if a B10D value is available and the operating time is less than 20 years.
 
Commissioning is prohibited until the machine has been checked in accordance with the regulations set out in the relevant EU directives / national laws.
 
The safety instructions contained in the technical documentation must be observed.
 
Using the examples does not exempt the user from careful project planning. For possible damages and consequential damages Lenze assumes no liability to the extent permitted by law.
 