The RFGPH1 function block does not reach its final value

Which products are affected?
EVS93xx-EK V7.1, EVS93xx-CK V7.1

What happens?
The RFGPH1 function block does not act as described in the documentation. Neither the final value requested at the RFGPH1-OUT is reached nor is the selected distance at the RFGPH1-DIST adhered to.

When does the problem occur?
The problem occurs at RFGPH1-IN in case of the distance-controlled ramp adjustment (RFGPH1-T/DIST = TRUE) and changing input values while the adjustment is executed.

Possible diagnostics?
The signal at the RFGPH1-OUT function block output stationary does not reach the setpoint selected (RFGPH1-IN input).

Short-term measures/recommendations?
In case of the RFGPH1 function block (RFGPH1-T/DIST = FALSE) it is recommended to use the time-controlled ramp function instead of the distance-controlled ramp function.

Evaluation:
Not critical with regard to function described since only the display value is affected.