Which products are affected?
8200vector 0.25 kW-11 kW (as of SW 3.7), 8200vector 15 kW-90 kW (as of SW 3.6), 8200motec (as of SW 3.7)
Function description:
The delay for a parameter set change over can be switched on (C0311 Bit 3 = 0) or off (C0311 Bit 3 = 1) under code C0311 bit 3:
- Code C0311 Bit 3 value '0' (+ 0): The first parameter set changeover is executed without delay. Following changeovers are performed with a delay of 20ms (new as of SW 3.7).
- Code C0311 Bit 3 value '1' (+ 8): The parameter set changeover is always executed without delay (similar to SW 3.1).
According to the Lenze default setting code C0311, bit 3 is set to '0' in software version V3.6/V3.7.
Applications
Parameter set changeover while the frequency inverter is running.