Question:
Can you use a HMI (e. g. EPM - H310) with an inverter 8200 / 8200 vector or motec (connected with EMF2171IB or EMF2175IB) to set the speed of the motor?

Answer:
It is no problem to use the AIF modules EMF2171IB or EMF2175IB for the communication between an operating terminal and the 8200. With both modules you can transfer data via parameter channel or process data channel.
In the Project Manager of the HMI Designer you have to connect the AIF modules to the CAN-port as if they were drives (as DEVICE_CAN_SLAVE or DEVICE_CAN_MASTER). In the HMI Designer Project there is no difference between connecting the HMI CAN-port to a FIF module, an AIF module or an Onboard port of a drive.