Armature chokes, typical temperature during operation of armature chokes

Question:

Which typical surface temperatures are normal / uncritical for armature chokes?

Answer:

The isolation materials used for Lenze armature chokes (order designation: ELA1-...) correspond to isolation class F, this means die limit of temperature rise is 100 K or the limit of temperature is 155 °C respectively. A surface temperature of 85 °C is typical, only temperatures of more than 100 °C lead to a restricted life time.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/20011602/1/