PLC-Designer: Error occurred when compiling with i950 V01.13 (1.6) EtherCAT slave (fixed from device description V01.13 (1.7))

Removed from:
i950 EtherCAT-Slave device description  from V01.13 (1.7)  (lpk-file for PLC-Designer)
Behavior of the new version:

The firmware package version V01.13.00.3463 is now correctly preset.



Description of the behavior:
PLC-Designer:
When compiling of a project with an i950 EtherCAT slave V01.13.00, an error occurs occurs during compilation:

  • Firmware file 'i950_v_1.13.0.3457_firmware.tar.gz' for device <device name>... is missing

The cause is the entry of the incorrect firmware package version V01.13.00.3457 in the device description i950 EtherCAT Slave V01.13 (1.6) (lpk file for PLC Designer).
There is no firmware package for this non-released version is stored.

Conditions under which the behavior occurs:

  • Im Lenze package server, the device description i950 V01.13 (1.6) is installed
  • In the PLC-Designer project, i950 EtherCAT slaves i950 base and/or i950 TA CiA402 Advanced are attached (a firmware download from the controller to other i950 is not supported) 
Betroffene Produkte:
i950 EtherCAT-Slave Device description V01.13 (1.6) (lpk-file for PLC-Designer)

Short-term measures, Recommendations, Rating:
The firmware package version setting in the Firmware/Parameters dialog of the i950 EtherCAT slave can be manually adjusted to the correct version V01.13.00.3463 if 'Settings from parameter 0x5820.1 or C640.0' is selected instead of 'never'.

Version_lpk_i95CiAAdv.png



[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500260/1/