WKC error every time EtherCAT is started if IO3000 is connected

Removed from:

Behavior of the new version:



Description of the behavior:
The following error is output when the EtherCAT is started:
0x30001595 EtherCAT_master: Cyclic command WKC error - Command: LRW-Address: 10800 - WKC act/set=2/3

This message is entered in the logbook of the controller. This lights up the error LED.

 

Conditions under which the behavior occurs:

An IO3000 Buskoppler (w580-C-FB-001) on the EtherCAT of a Lenze controller.


Affected products:

IO3000 bus coupler (w580-C-FB-001) 


Short-term measures, Recommendations, Rating:

This behavior is not critical in itself. The EtherCAT goes into operational mode. The error message  can be acknowledged using the function block L_IE1P_ResetErrorGlobal from the L_IE1P_ApplicationErrors library . The red error LED on the controller will also go out.

Note: No fix is planned for this behavior.



[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202400379/1/