i950: Activate quick stop (QSP) via digital input of the inverter (DI) (from V01.11.00)

Function-extension:
The CiA quick stop function (QSP) can now also be controlled via a digital input on the inverter (DI) if required.

The following objects are available for parameterization:

  • 0x2632:x      Inverting the logic
  • 0x2633:x       Debounce time
  • 0x263B:x       Activate digital input manually
  • 0x282C:1       Application Level Digital Inputs
  • 0x2DE1:002: CiA402: QSP via DIGIN Enable
The two control signal sources for activating the quick stop function (digital input and control bit in control word 0x6040) are OR-linked.

Contained in the following products:
Servo Inverter i950 FW:  from  V01.11.00 

Application:
applications in which the quick stop function (QSP) is to be activated via a digital control input directly on the inverter.


[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500015/1/