EtherCAT master is not automatically updated with the controller

Removed from:
Cabinet Controller c300 V3.21.3 with device description from V3.21.5.6
Cabinet Controller 3200C V3.21.3 with device description from V3.21.5.6
Panel Controller p300 V3.21.3 with device description from V3.21.5.6
Panel Controller p500 V3.21.3 with device description from V3.21.5.6

Cabinet Controller c430 from V1.11
Cabinet Controller c520 from V1.11
Cabinet Controller c550 from V1.11

Behavior of the new version:
When opening an existing PLC Designer project with an update to the controller versions described above , the EtherCAT master is updated correctly.

Description of behavior:
In the PLC Designer project, the version of the device description of the EtherCAT master does not match the version of the controller.

Under what conditions does the behavior occur?
If an existing PLC Designer Project is opened and updated with an older controller and EtherCAT master version, the EtherCAT master version may not be set correctly. This can lead to inconsistencies in the controller and EtherCAT master version. This in turn can lead to error messages.
 
Affected products:
Cabinet Controller c300
Cabinet Controller 3200C
Cabinet Controller c520
Cabinet Controller c550

Panel Controller p300
Panel Controller p500

Short-term measures, Recommendations, Rating:
Select the 'EtherCAT_Master' object and update this object using the corresponding command in the context menu.