Safety IO modules: Display of the FSoE address

Corrected from:

Behavior of the new version:




Description of behavior:
 It is not possible to display the FSoE address set via the DIP switch on the side of the module via an index using the PLC Designer / EASY Starter.

Conditions under which the behavior occurs:

  • The behavior occurs permanently.

 
Affected products:
Safety IO modules C25BAYA42/82/160/164
Short-term measures, Recommendations, evaluation:

The FSoE address set via the DIP switch can, for example, be read out by the PLC program in the standard controller using an SDO read command, The FSoE address is located at index 0xF980:1. This short-term measure is not available with the C25BAYA42 module.

By reading out the set FSoE address, an incorrectly set DIP switch can be quickly detected when the machine is commissioned or serviced.


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202400317/1/