OPC UA - Calling methods from imported user information model

Corrected from:

Behavior of the new version:




Description of the behavior:

The call of an OPC UA Server method by a Client results in a "BadNoEntryExists" error status code.

 
Conditions under which the behavior occurs
  • In the PLC Designer - Mapping Editor a predefined OPC UA user model with a method is imported.
  • The method is mapped to a matching method function block in the PLC application.
  • The PLC Designer project is downloaded to the Controller.
  • A Client is connected to the Controller OPC UA Server with the loaded user model.
Affected products:

Short-term measure, recommendations, evaluation:
 Delete the method in the imported user model and create a new one with the PLC Designer - Mapping Editor.