What happens?
The IO 1000 module cannot be put into operation The red MF Lead on the module lights up.
The parameters of the module look as follows:
- Baudrate: ?
- Protocol: ?
- Data bits: 5
- Stop bit: Not defined
- Option 5: 0
- Option 6: 0
When does the behaviour occur?
The module EPM-S640 resp. EPM-S650 is inserted on the CAN bus of a Lenze Controller (PLC Desginer V3.x).
Which products are affected?
EPM-S640
EPM-S650
Short-term measures:
Set options 5 and 6 to the values specified in the IO 1000 system manual, e.g.:
- Option 5: 250
- Option 6: 1
Set the baud rate, protocol, data bits, ... to the desired values.
Hint: There is no change planned for this behaviour.