Eliminated from:
E94AYCER communication module FW 1.30.05
Behaviour of the new version?
By means of the new firmware 1.30.05 the Engineer project can completely be uploaded from the 9400.
Which products are affected?
E94AYCER communication module FW 1.30.04
What happens?
The communication is interrupted when parameters are uploaded by means of the Engieer via Profinet.
This behaviour was caused because the module could not transmit the max. file size of the project to be uploaded.
When does the problem occur?
If a project is to be uploaded via Profinet by means of the Engineer.
Possible diagnostics?
If the upload is not completed successfully, the behaviour described before has occurred.
Short-term measures/recommendations?
None.
Evaluation:
Since this function restriction refers to project planning access and / or diagnostics access processes between Engineer and communication module, a malfunction of the plant will not occur.