Function extension:
Diagnostic data can now be assigned to the second CAN process data channel, 'CAN2-OUT', which had not been used so far.
The diagnostic variables can be assigned to the eight data bytes of the CAN2-OUT via C0390/x.
The following diagnostic variables (1 or 2 byte) can be selected:
- C0390/x = 0: Not assigned
- C0390/x = 1: Voltage V-L1/L2
- C0390/x = 2: Voltage V-L2/L3
- C0390/x = 3: Zero crossing counting per second (frequency measurement of V-L1/L2)
- C0390/x = 4: Mains synchronisation, n times outside the limits (evaluation of Vsd and Vsq)
- C0390/x = 5: Internal status bits
- C0390/x = 6: Transformed voltage component Vsd
- C0390/x = 7: Transformed voltage component Vsq
- C0390/x = 8: Internal error bits
One by one, the eight available data bytes of the PDO are filled with user data. Due to the differing variable sizes (1 or 2 bytes), the variables selected in the last subcodes of C0390/x may not be displayed completely.
Code C0391 displays in per cent how many bytes of the CAN2-OUT have already been assigned.
A non-zero cycle time must be set in C0356/2 to activate the CAN2-OUT.
In which products/versions is it included?
ECS power supply module from V5.0