OPC-UA Server reports out of memory due to many files on the SD card
Removed as of:
as of V1.8
Behavior of the new version:
Description of the behavior:
Will be stored on the SD card under automatically generated directories (e.g. plc/prg/prg).If too many files are stored on the SD card under automatically generated directories (e.g. plc/prg/pta1), this can lead to memory utilization so that the OPC UA server shuts down and reports an "out of memory" error. This occurs, for example, when a large CODESYS Visu project is saved on the SD card.
Under what conditions does the behavior occur?
Many files on the SD card under automatically generated directories
Taxonomy:
Controller c520
,
Controller c550
,
Controller c500
,
Controller c750
,
System
AKB-ID:
202200152