SYSTEM_bPLCResetAndRun without function (remedied from B-SW V7.0)
Remedied from:
ECS axis module B-SW V7.0
Behaviour of new version?
If the SYSTEM_bPLCResetAndRun system variable of the SYSTEM_FLAGS system block is set to TRUE a control reset with immediate restart of the PLC target system is activated.
After the restart the system POU PLC_ColdStart is executed first.
Which products are affected?
ECS axis module B-SW <= V6.7
EVS93xxEI (Servo PLC V6.x)
EVS93xxET (Servo PLC V6.x equipped with technology function)
EPL-10200 (Drive PLC V6.x)
What happens?
The SYSTEM_bPLCResetAndRun system variable of the SYSTEM_FLAGS system block is designed to execute a control reset and to restart the PLC target system.
If the SYSTEM_bPLCResetAndRun system variable is set to TRUE a control reset is not activated. The PLC target system continues to run irrespective of the system variable state.
When does the problem occur?
The SYSTEM_bPLCResetAndRun system variable is without function.
Possible diagnostics?
None.
Short-term measures/recommendations?
Use code C2108 to reset and restart the PLC target system.
Evaluation:
By means of the SYSTEM_bPLCResetAndRun system variable the PLC target system can be reset without mains connection. This variable is quite seldom used in practice.
Taxonomy:
ECSxA application
,
ECSxE power supply module
,
ECSxK capacitor module
,
ECSxM motion
,
ECSxP position and shaft
,
ECSxS speed and torque
,
ECS servo inverters
AKB-ID:
200603130
Last update:
2023/09/08
Category:
Informations sur la version
Lenze reserves the right to change information on this page at any time. Any liability for the accuracy of the information is excluded.