Keypad: Wrong display after TRIP reset (remedied from B-SW V7.0)
Remedied from:
ECS axis module V7.0
Behaviour of new version?
No wrong display after TRIP reset will occur.
Which products are affected?
ECS axis module V3.0
What happens?
A pending interference is still incorrectly indicated with 'fail' by the operating and display unit (keypad) even though a TRIP reset has been executed.
When does the problem occur?
If the TRIP reset has been carried out once.
Possible diagnostics?
The drive can be operated as usual although the keypad indicates an error.
Short-term measures/recommendations?
Carry out several TRIP resets.
Evaluation:
This is only a display error. The wrong indication can be eliminated by applying the simple measure mentioned above.
Taxonomy:
ECSxA application
,
ECSxE power supply module
,
ECSxK capacitor module
,
ECSxM motion
,
ECSxP position and shaft
,
ECSxS speed and torque
,
ECS servo inverters