OPC UA mapping - Space in base model name => Compiling error
Fixed from: V4.1
Behavior of the new version: The input of the file name is checked and a pop-up is displayed if the input is invalid.
Description of the behavior:
If there is a space in the name of the basemodel that was imported, then there is a compiler error when compiling. Unfortunately, the error information gives no indication of the cause.
Conditions under which the behavior occurs: => Space in basemodel name
Affected products:
PLC Designer version V4.0 and higher
Short-term measure, recommendations, evaluation:
Remove spaces from the basemodel name and then import this basemodel before the basemodel with the space in the name has been deleted. Then have PLC Designer translate the project.